Model Number |
hd006 |
Product Description
Technical parameters: 1. Rated Voltage: 24kV 2. Rated Frequency: 50Hz 3. Rated Insulation Level Power Frequency Withstanding Voltage (1 min): 50kV Lightning Impulse withstanding Voltage: 125kV 4. Main Busbar Rated Current: 630, 1250, 1600, 2000A Branch Busbar Rated Current: 630, 1250, 1600, 2000
5. 3s Heat Steady Current (Virtual value): 16, 20, 25KA 6. Rated dynamic Steady Current (peak value)*: 40, 50, 63KA 7. Degrees of Protection: IP4X is for enclosure. The protection degree between every compartment is IP2X. It is also IP2X when the door of the breaker room is open
Introduction: HKA-24 Metal-clad Enclosure Switchgear is advanced high-voltage switchgear that Beijing Huadong Electric Co., Ltd. has independently worked out and developed. It applies to the electric power system of 3 phase AC 50Hz. It is mainly used to receive, distribute the electric energy as well as control, protect and monitor the circuit.
HKA-24 Switchgear boasts various ways to prevent misoperation, including preventions on movable truck and earthing switch under load operaion, on the closing of earthing switch at the closing position of breaker.
HKA-24 Switchgear is equipped with withdrawable VD4, VH4 or SF6 breakers of high performance. The secondary loop of the switchgear is fixed with advanced and reliable protective components. HKA-24 Switchgear is a power distribution equipment, combining high technology, stable performance and reasonable structure. It is easy to use, safe and reliable
Introduction of Standard and Criterion: HKA-24 Switchgear is designed and made according to the following standards:
International Electrotechnical Commission Standard.
IEC62271-200 rated voltage (more than 1KV and less than 52KV) AC metallic enclosure switchgear and control equipment.
IEC60694: 2002 common technical requirment for high-voltage switchgear and control equipment.
IEC62271-100: 2001 high-voltage switchgear and control equipment-the 100th section: High-voltage AC breaker.
|